Power Network Application Trainer
– Earthing / Grounding network impedance measurement
126
Figure 80-2: Auto sequence setup (4-pole, HF and S-Flex)
Measuring procedure
1. Connect the test object for performing 4-pole, HF
– 25 kHz and S-Flex measurement.
Connection details could be found under 4.1.2, 4.1.3 and 4.1.5 Item.
2. Select the Auto Sequence menu and select already prepared “8.2.2.6. Tower FOP /
HF 25 kHz / 1xFlex clamp IEEE 81
” sequence.