Measurement at fixed frequency 329 Hz:
Expected result for
single
frequency measurement:
Since there is additional inductive part added to the earth resistance, earth impedance
is higher than the result measured in exercise Nm.1, item 4.1.1.1.2.
Measuring procedure
– sweep frequency measurement:
Measurement setup and procedure is the same as under exercise Nm. 1 (Item
4.1.1.1.2), so check the details for proper connection.
Expected result:
Earth impedance measurement in frequency range from 55 Hz up to 15.4 kHz shows
prominent inductive character of measured object.
We propose to use “sweep mode” measurement for analysing the earth impedance
character, to see the test object characteristic also at the higher frequencies.