Power Network Application Trainer
– Earthing / Grounding network impedance measurement
69
3 Earth Potential
Correct earthing of exposed conductive parts of the object assures that the voltage on
them stays below dangerous level in case of a fault (short-circuit current, lightning
strike). If fault happens a short-circuit current will flow through the object and equipment
into the earthing electrode. The earth resistance is non-zero, so current injected into the
earth at the grounding electrode produces a potential rise related to a distant reference
point.
Earth resistance is not concentrated in one point but it is distributed around whole
electrode. If a faulty current flow through the earth electrode, then a typical distribution
of the voltage occurs around it (voltage funnel). Maximum voltage drop is concentrated
around the earth electrode.
A typical voltage distribution occurs around the electrode, so called “voltage funnel”.
Fault currents close to power distribution objects (substations, distribution towers,
plants) could be very high, up to 200 kA. This can result in dangerous step and contact
voltages. If there are underground metal connections (intended or unknown) the voltage
funnel can get atypical forms and high voltages can occur far from the point of failure.
Therefore, the voltage distribution in case of a fault around these objects should be
carefully analysed.
Figure 50-2: Dangerous voltages on a faulty earthing system
where:
U
S
…. Step Voltage in case of a fault current
U
C
.... Contact or Touch Voltage in case of a fault current
U
F
.... Fault voltage
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...