Power Network Application Trainer
– Earthing / Grounding network impedance measurement
103
Note:
Since the limit value selected, there is no PASS/FAIL indication. Measured impedance
value is much under the expected one. Additional, MI 3290 generate four alarms, which
could indicate the problematic measurement:
The measurement range of the instrument is exceeded.
Low current through Flex clamps. Result may be impaired.
High electrical noise was detected during measurement. Results may be impaired.
Expected result for foot number 4:
To get total object impedance, we need to calculate it from the individual values. Four
foots pylon could be presented as parallel connection of four impedances, so the
calculated object impedance is:
Foot Nm. 1
17,8
Ω
Foot Nm. 2
390
Ω
Foot Nm. 3
283
Ω
Foot Nm. 4
5,33
Ω
Total impedance
3,99
Ω
Table 26-
2: Pylon foot’s impedance
Measuring pylon resistance is time consuming procedure; since for each measurement
we need to move flex clamps to the next foot. Performing measurements in real
environment using all four flex clamps, enables additional specific foot resistance
analyse and detecting wrong (bad) earthing.
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...