Power Network Application Trainer
– Earthing / Grounding network impedance measurement
63
Figure 44-2: Substitute circuit for Passive (Flex Clamps) measurement
Notes:
Inductive current I
gw
flows into earth through Z
sel1/1
, Z
sel2/1
, Z
sel1/2
and Z
sel2/2
The voltage drop is measured by auxiliary potential probe (S).
The selective currents I
f1-4
is measured through the earthing electrode Zsel
1-4/1
(pylon foots) selected by the user.
The selected earth impedance Z
sel1-4/1
is determined from the voltage U
S
–E
and
selected current (external current clamp
– I
f1-4
) ratio.
When using only one, two or three flex clamps, always connect one clamp to F1
terminal (synchronization port).
Make sure that the arrow marked on the clamp coupling points toward the correct
orientation for correct phase measurement.
Make sure that the number of turns is correctly entered in the test parameters
window