Power Network Application Trainer
– Earthing / Grounding network impedance measurement
104
4.1.3.3 S
– Flex measuring method by using one Flex-clamp - regular
foot resistance/ - resistive earthing type - simulated ground
wire connection
Figure 69-2:S-Flex measurement setup
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistive earth
character), flex measurement,
simulated ground wire connection
Pylons (mono and multi-leg)
with and without protective earth
cable connection
Ski lifts
Radio towers
Foot Nm. 1 approx.30,1
Ω
Foot Nm. 2 approx.11,7
Ω
Foot Nm. 3 approx.23,6
Ω
Foot Nm. 4 approx. 5,63
Ω
Z
tot calc
= 2,95
Ω
Table 27-2: S-Flex measurement setup/result presentation
Measuring procedure
1. Follow the measurement setup connection described under 4.1.3.1 exercise. Connect
setup switches and ground wire accordingly.