Power Network Application Trainer
– Earthing / Grounding network impedance measurement
131
4.1.7 Impulse measuring method
Figure 81-2: Impulse measuring method setup
This exercise presents procedure how to perform impulse measuring method.
The impulse impedance of an earthing system is a useful parameter, to predict the
behaviour in transient conditions, such as direct lightning strike into the tested object.
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistance /
inductive earth character), Impulse
measurement
Industrial areas
Transformer stations
Radio towers
Pylons with/without protective
earth cable connection
Solar power plants
Wind & water turbine
Z
p
= 3,7 Ω
Z
p
= 112
Ω
Table 44-2: Impulse measuring method setup/result presentation
Switch setup position:
1. Under
Pulse
test function select the
Zp
(
Impulse Measurement)
measurement
method.