Power Network Application Trainer
– Earthing / Grounding network impedance measurement
111
4.1.3.5.2 S
– Flex measuring method by using one Flex-clamp with
simulated
regular pylon’s foot condition and resistance
earth character
– measuring of all four foots together
Figure 72-2: S-Flex measurement setup for measuring all pylon foots
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistive earth
character), flex measurement,
simulated ground wire connection
Pylons (mono and multi-leg)
with and without protective earth
cable connection
Ski lifts
Radio towers
Z
tot calc
= 2,65 Ω
Table 34-2: S-Flex measurement setup/result presentation
Measuring procedure
1. Follow the measurement setup connection described under 4.1.3.1 exercise. Connect
setup switches and ground wire accordingly. Take care that flex-clamp will be installed
around all four pylon legs.