Power Network Application Trainer
– Earthing / Grounding network impedance measurement
129
To get total object impedance, we need to calculate it from the individual values. Four
legs pylon could be presented as parallel connection of four impedances, so the
calculated object impedance is:
Foot Nm. 1
14,76
Ω
Foot Nm. 2
348
Ω
Foot Nm. 3
1,767k
Ω
Foot Nm. 4
6,62
Ω
Total impedance
4,49
Ω
Table 42-
2: Pylon’s foot impedance calculation