Power Network Application Trainer
– Earthing / Grounding network impedance measurement
74
Figure 55-2: Step voltage measurement with MI3295S & MI3295M instruments
Contact voltage
is defined as potential difference between the ground potentialof a
grounding system- the surface potential where a person could stand while at the same
time having a handin contact with a grounded structure or object.
The measurement of contact voltage is performed between an earthed accessible metal
part and ground 1 meter apart from the tested object. The voltage between the probes
is measured by a voltmeter with an internal resistance of 1 kΩ that simulates the body
resistance (test step/contact voltage plates or 25kg probes should be used).
Figure 56-2: Contact voltage measurement with MI3290 instrument
Figure 57-2: Contact voltage measurement with MI3295S & MI3295M instruments