Page 7.1 - 20
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Operating and appliance data
7.1.7 Description of the SY (System) - Parameters
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
SY.01
Watchdog cycle
0001h
RO
-
-
0000
255
1
hex
-
The monitoring of communication in the synchronous bus operation occurs with parameter SY.01, which is
evaluated in a field bus operator (e.g. DIASBus). Triggering of the malfunction occurs via Pn.05, Pn.06, SY.57,
like monitoring of the external interface at standard operators. The function is switched off at a power on reset
(SY.01 = 0). A value > 0 switches on the monitoring. The number of cycles is adjusted that shall occure until
a malfunction is triggered.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
Sy.02
Inverter identifier
0002h
RO
-
-
0000
9999
1
hex
-
An unique number is assigned to each type of frequency inverter which identifies the inverter. This value is
used for example by COMBIVIS to load the correct configuration files.
Sy.02 can be written with the indicated
value (e.g. for identification of download lists).
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
Sy.03
Power unit code
0003h
RO
-
-
-255
255
1
-
-
On the basis of the power circuit identification the control recognizes the used power circuit respectively a
change of the power circuit and adjusts certain parameters accordingly. To accept a new P-Id enter positive
values (see chap. 8 „E.Puch“).
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
Sy.04
Configuration data se
-
lection
0004h
RO
-
-
0
24
1
-
-
SY.05
Configuration data
0005h
RO
-
-
-32727
32767
1
-
-
This parameters give information about the appropriate config-data of the inverter.
Parameter
Addr.
R
PG
E
Min. value
Max. value
Res.
[?]
Default
Sy.06
Power unit code
0006h
RW
-
+
0
239
1
-
1
The address if the inverter shall be responded via "COMBIVIS" or another control can be adjusted in SY.06.
Values between 0 and 239 are possible, the default value is 1. If several inverters are operated on the bus
simultaneously, it is absolutely necessary to assign different addresses to them, since otherwise it leads to
communication failures because several inverters may answer at the same time. The description of the DIN
66019II protocol (C0.F5.01I-K001) contains further information to this.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...