Troubleshooting
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 8.1 - 3
8
8.
Error Assistance
The following chapter shall help you to avoid errors as well as help you to determine and remove the cause
of errors on your own. The error messages of
all
KEB COMBIVERT F5 are represented, although depending
upon device and design some are missing.
8.1
Troubleshooting
8.1.1 General
If error messages or malfunctions occur repeatedly during operation, the first thing to do is to pinpoint the exact
error. To do that go through the following checklist:
- Is the error reproducable?
For that reset the error and try to repeat it under the same conditions. If the error can be reproduced, the next
step is to find out during which operating phase the error occurs.
- Does the error occur during a certain operating phase (e.g. always during acceleration)?
If so, consult the error messages and remove the causes listed there.
- Does the error occur or disappear after a certain time?
That may be an indication for thermal causes. Check, whether the inverter is used in accordance to the ambient
conditions and that no moisture condensation takes place.
8.1.2
Error Messages and their Cause
At KEB COMBIVERT error messages are always represented with an "E." and the appropriate error in the
display.Error messages cause the immediate deactivation of the modulation. Restart possible only after reset.
Malfunction are represented with an " A." and the appropriate message. Reactions to malfunctions can vary.
Status messages have no addition. The status message shows the current operating status of the inverter (e.g.
forward constant run, standstill etc.).
The display and their cause are described in the following:
Display
COMBIVIS
Value Meaning
Status messages
A.Acc
Warning! maximum
acceleration
106
Maximum acceleration exceeded
A.SCL
Warning! speed controller
limit
107
Speed controller limit reached
bAC
blockade recognized
129
The setpoint must be above level Pn.86.
If the actual value is below the level, the counter starts. If the counter
reaches the adjusted time in Pn.86, a blockade is recognized. The
output function do.00...07 = 96 (blockade active) is set. On exceeding
the limit the value of the counter decreases.
bbL
base block
76
Power modules for motor de-excitation locked
bon
close brake
85
Brake control, brake engaged (see chapter 7.15.5)
boFF
open brake
86
Brake control, brake engaged (see chapter 7.15.5)
further on next side
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...