Protective functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.13 - 21
7
7.13.5.3
Time monitoring abnormal stopping
For safety, a maximum time for the abnormal stopping-function can be programmed.
Pn.68: Max. abn. stopping time
Value
Explanation
0,01...100,00 s
time after which the inverter switches from malfunction- ("abnormal stop" A.XX) to the
error state (E.XX)
If the inverter is still in the malfunction state (A.XX) after this time (no RESET or automatic restart was exe-
cuted), the inverter switches off the modulation and changes to the corresponding error state (A.XX => E.XX).
7.13.5.4
S-curve for quick stop ramp
Pn.83: Quick stop ramp for s-curve
Value
Explanation
0...5.00 s
Quick stop s-curve time is valid for the quick stop ramp (Pn.60), set-programmable
7.13.5.5
Abnormal stopping via control word
Abnormal stopping can also be triggered via the control word (SY.43 and SY.50, respectively ). Then, the status
displays "79: abnormal stopping" (StOP).
The behaviour for abnormal stopping via control word can be defined
in parameter Pn.58 „quick stop mode“.
Abnormal stopping mode determines the behaviour for abnormal stopping via control word.
Pn.58: Quick stop mode
Bit
Meaning
Value
Explanation
2
Quick stop via con-
trol word (SY.50)
0: Sy.50 modulation off
disabling of modulation after reaching speed 0
4: Sy.50 modulation on
Fast stop with holding torque on reaching speed 0
7.13.6
Speed search
The speed search permits a relatively smooth engagement of the frequency inverter onto a running motor.
Without activation of the speed search, the motor is always slowed down first. In closed-loop operation with
encoder, this occurs at the torque limit, in closed-loop operation without encoder, the motor must be stopped
with DC-current braking.
On activation of the speed search, however, the current speed is determined and the drive is accelerated or
decelerated from this starting point to the setpoint speed, according to the adjusted ramps.
Parameter Pn.26 "Speed search starting condition" determines after which events the speed search is to be
executed.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...