Page 7.3 - 34
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Digital in- and outputs
do.00...do.07: Switching conditions
V a -
lue
Function
Description
18
Brake control
The output is used for brake control. The output becomes active if the brake
is to be ventilated.
19
System deviation > level
ru.02 „ramp output display“ – ru.07 „actual value display“ > switching level
20
Constant run
Is set, if parameter ru.07 „actual value display“ is in a window of +/- LE.16
„hysteresis“ around ru.01 „set value display“. Not set in state "no control
release" or "standstill". The state of the condition is undefined if the ramp
generator is deactivated by another function (e.g. positioning, speed search,
DC braking, etc.).
21
Acceleration
Ramp generator is in phase forward acceleration, reverse acceleration or
acceleration stop.
22
Deceleration
Ramp generator is in phase forward deceleration, reverse deceleration or
deceleration stop.
23
Real direction of rotation = set
direction of rotation
The directions at the input and at the output of the ramp generator are the
same (the sign of ru.02 „ramp output display“ is identical with the sign of
ru.01 „set value display“).
24
Utilization > level
Utilization (ru.13) > level
25
Amount active current > level
Amount active current (ru.17) > switching level
26
DC link voltage > level
Actual DC voltage ru.18 > switching level
27
Actual value > level
actual value display (ru.07) > switching level
28
Set value > level
Amount set value (ru.01) > switching level (only valid if the ramp generator
is active)
29
Approach to reference point fi
-
nished
Approach to reference point executed and completed (position valid/ soft-
ware limit switch useable)
30
actual torque > level
actual torque > switching level (not in v/f characteristic open-loop operation)
31
Absolut value AN1 > level
Amount AN1 / AN2 / AN3 at the
output of the characteristic amplifier > swit
-
ching level
32
Absolut value AN2 > level
33
Absolut value AN3 > level
34
AN1 > level
AN1 / AN2 / AN3 at the
output of the characteristic amplifier > switching level
(with sign evaluation)
35
AN2 > level
36
AN3 > level
37
Timer 1 > level
ru.43 „timer 1 display“ or ru.44 „timer 2 display“ > switching level
38
Timer 2 > level
39
Angle difference > level
Amount ru.58 „angle difference“ > switching level (observe only in posi- or
synchronous mode / scaling factor of the LE-Parameters for increments)
40
Hardware current limit active
Protective function „hardware current limit“ is active
41
Modulation on
is set, if the modulation is active
42
ANOUT3 PWM
Output of the analog signal ANOUT 3 or ANOUT 4 as PWM signal. The peri-
od can be adjusted with An.46 or An.52.
43
ANOUT4 PWM
44
Inverter state (ru.0) = level
Number of the inverter state (e.g. 18 at error! Watchdog) = switching level
45
Power module temperature
(ru.38) > level
Power module temperature (ru.38) > switching level
46
Motor temperature (ru.46) > le-
vel
Motor temperature (ru.46) > switching level
further on next side
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...