Network components
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 10.1 - 9
10
10.1.9 Bus parameter
10.1.9.1
Inverter address (SY.06)
In SY.06 can be adjusted, if the inverter shall be responded via "COMBIVIS" or another control. Values between
0 and 239 are possible, the default value is 1. If several inverters are operated on the bus simultaneously, it is
absolutely necessary to assign different addresses to them, since otherwise it leads to communication failu-
res, because several inverters may answer at the same time. The description of the DIN 66019II protocol (C0.
F5.01I-K001) contains further information to this. SY.06 is not reset on loading the default parameters.
10.1.9.2
Baud rate ext. bus (SY.07)
Following values for the baud rate of the serial interface are possible:
SY.07: Baud rate ext. bus
Value
Baud rate
0
1200 Baud
1
2400 Baud
2
4800 Baud
3 (default)
9600 Baud
4
19200 Baud
5
38400 Baud
6
55500 Baud
If the value for the baud rate is changed via the serial interface, it can be changed again only via keyboard or
after adapting the baud rate of the master, because no communication is possible with different baud rates of
master and slave.
Should problems occur at the data transmission choose a transfer rate of maximal 38400 baud.
10.1.9.3
Baud rate int. bus (SY.11)
The transmission speed between operator and inverter is determined with the internal baud rate. The following
values are possible (unit-dependent):
Va-
lue
Baud rate
Value Baud rate
Va-
lue
Baud rate
3
9,6 kBaud
6
55,5 kBaud
9
115,2 kBaud
4
19,2 kBaud
7
57,6 kBaud
10
125 kBaud
5
38,4 kBaud
8
100 kBaud
11
250 kBaud
10.1.9.4
Watchdog time (Pn.06)
For continuous control of the communication at the operator interface it is possible to trigger an error message
of the inverter, without incoming telegrams after expiration of an adjustable time (0.01… 10 s). The function can
be deactivated by setting the value "off".
10.1.9.5
Response to E.bus (Pn.05)
This parameter determines the response to a watchdog error. The message E.buS or A.buS is output depen-
dent on the selected adjustment.
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...