Special functions
© KEB, 2012-10
COMBIVERT F5-A, -E, -H
Page 7.15 - 5
7
1
The braking time is dependent on the actual frequency (ru.03), not from the actual speed (ru.07). The
reference value for the calculation of the braking time, however, is a speed (dependent on ud.02 "control
type", for "4: F5-M / 4000rpm“ is the reference value 1000 rpm). To calculate the braking time, the actual
frequency (ru.03) must be converted to a speed according to the following formula:
ru.03 * 60
———————————
pole-pair number of the
motor
2
Actual braking time = Pn.30 * ru.03 * 60 / pole-pair number of the motor / reference value (The reference
value is dependent on ud.02 "control type". The reverence value in 4000 rpm mode is 1000 rpm and 2000
rpm in 8000 rpm mode etc.)
3
Actual braking time = Pn.30 * Pn.32 / reference value (The reference value is dependent on ud.02 "con-
trol type". The reverence value in 4000 rpm mode is 1000 rpm and 2000 rpm in 8000 rpm mode etc.)
4
These adjustment are operative only if in Bit 0...3 "DC-brake mode" the value "10: conditions" is chosen.
If the same condition is also set for speed search, DC-brake has priority.
7.15.1.1
V/F characteristic control
In v/f-characteristic control, a DC voltage is applied to the motor. The max. braking voltage is set with Pn.31
"DC braking max voltage".
The current is limited only by the inverter. If the inverter is oversized compared to the motor, the maximum bra-
king voltage (Pn.31) must be decreased to avoid overheating of the motor.
At large ratings the maximum braking voltage can lead to overcurrent errors (E.OC). In that case reduce it with
Pn31.
7.15.1.2
Speed-controlled operation without
feedback
(ASCL)
In ASCL-mode, a DC current is impressed on the motor.
The braking current is set with Pn.33 "DC-brake max. current ASCL". The current can be preset in a range of
0...400.0% with respect to the rated motor current (dr.00).
The current is limited above by the permissible standstill current (see technical data of the corresponding inver-
ter) or by dr.37 "maximum current", if in dS.03 the maximum current mode is activated. The lower limit is given
by the magnetising current.
After completion of the DC braking function, the rated flux of the machine must flow before the motor is started.
To that end, "Wait for magnetisation = 128: on" (Bit 7 = 1) must be programmed in parameter dS.04. The tor-
que display is not valid in the DC braking (display always = 0 Nm).
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...