Page 8.1 - 6
COMBIVERT F5-A, -E, -H
© KEB, 2012-10
Troubleshooting
Display
COMBIVIS
Value Meaning
E.LSF
Error ! load shunt fault
15
Error: Load-shunt relay has not picked up, occurs for a short
time during the switch-on phase, but must automatically be reset
immediately. If the error message remains the following causes may
be applicable:
load-shunt defective
input voltage wrong or too low
high losses in the supply cable
braking resistor wrongly connected or damaged
braking module defective
E.ndOH
no ERROR drive overheat
11
Motor temperature switch or PTC at the terminals T1/T2 is again in
the normal operating range. The error can be reset now.
E.nOH
no E. over heat pow.mod.
36
Temperature of the heat sink is again in the permissible operating
range. The error can be reset now.
E.nOHI
no ERROR overheat int.
7
No longer overheating in the interior E.OHI, interior temperature has
fallen by at least 3°C
E.nOL
no ERROR overload
17
No more overload, OL-counter has reached 0%; after the error E.OL a
cooling phase must elapse. This message appears upon completion
of the cooling phase. The error can be reset now. The inverter must
remain switched on during the cooling phase.
E.nOL2
no ERROR overload 2
20
The cooling time has elapsed. The error can be reset.
E.OC
Error ! overcurrent
4
Occurs, if the specified peak current is exceeded. Causes:
acceleration ramps too short
the load is too big at switched off acceleration stop and switched off
constant current limit
short-circuit at the output
ground fault
deceleration ramp too short
motor cable too long
EMC
DC brake at high ratings active (see 7.15.5)
E.OF
ERROR! overfrequency
61
Current frequency is above the permissible range.
E.OH
Error ! overheat pow.mod.
8
Overtemperature of power module. Error can only be reset at E.nOH.
Causes:
insufficient air flow at the heat sink (soiled)
ambient temperature too high
ventilator clogged
E.OH2
Error ! motor protection
30
Electronic motor protective relay has tripped.
E.OHI
Error ! overheat internal
6
Overheating in the interior: error can only be reset at E.nOHI, if the
interior temperature has dropped by at least 3 °C.
E.OL
Error ! overload (Ixt)
16
Overload error can only be reset at E.nOL, if OL-counter reaches 0%
again. Occurs, if the overload is longer than the permissible time (see
technical data). Causes:
poor controller adjustment
mechanical fault or overload in the application
inverter not correctly dimensioned
motor wrongly wired
encoder defective
further on next side
Summary of Contents for COMBIVERT F5-A
Page 1: ...KEB COMBIVERT F5 A E H 4 4 APPLICATION MANUAL Mat No Rev 00F5AEA K440 1A...
Page 2: ...Page 1 1 2 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 4: ...Page 1 1 4 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 14: ...Page 1 1 14 COMBIVERT F5 A E H KEB 2008 02 Table of contents...
Page 20: ...Page 2 1 6 COMBIVERT F5 A E H KEB 2012 10 Product Overview...
Page 28: ...Page 3 1 8 COMBIVERT F5 A E H KEB 2012 10 Control Units...
Page 34: ...Page 4 1 6 COMBIVERT F5 A E H KEB 2012 10 Fundamentals...
Page 40: ...Page 4 2 6 COMBIVERT F5 A E H KEB 2012 10 Password input...
Page 42: ...Page 5 1 2 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 46: ...Page 5 1 6 COMBIVERT F5 A E H KEB 2012 10 Selection of Operating Mode...
Page 70: ...Page 6 2 20 COMBIVERT F5 A E H KEB 2012 10 Start up...
Page 140: ...Page 7 3 44 COMBIVERT F5 A E H KEB 2012 10 Digital in and outputs...
Page 238: ...Page 7 7 12 COMBIVERT F5 A E H KEB 2012 10 Speed control...
Page 254: ...Page 7 8 16 COMBIVERT F5 A E H KEB 2012 10 Torque display and limiting...
Page 260: ...Page 7 9 6 COMBIVERT F5 A E H KEB 2012 10 Torque control...
Page 292: ...Page 7 11 26 COMBIVERT F5 A E H KEB 2012 10 Speed measurement...
Page 432: ...Page 7 14 14 COMBIVERT F5 A E H KEB 2012 10 Parameter sets...
Page 466: ...Page 7 15 34 COMBIVERT F5 A E H KEB 2012 10 Special functions...
Page 478: ...Page 7 16 12 COMBIVERT F5 A E H KEB 2012 10 CP Parameter definition...
Page 488: ...Page 8 1 10 COMBIVERT F5 A E H KEB 2012 10 Troubleshooting...
Page 496: ...Page 9 1 8 COMBIVERT F5 A E H KEB 2012 10 General design...
Page 538: ...Page 11 1 28 COMBIVERT F5 A E H KEB 2012 10 Parameter...
Page 540: ...Page 12 1 2 COMBIVERT F5 A E H KEB 2008 02 Annex 12 1 1 Index 12 1 3...