5 Quick Commissioning
- 67 -
Operation
Para.
No.
Parameter Name
Default
Commission
0: No function
1: AC drive running
2: Fault output 1
(immediate output in coast to stop mode, output after stop in
decelerate to stop mode)
3: Frequency-level detection 1 output
4: Frequency reached
5: Zero-speed running (no output at stop)
6: Motor overload pending
7: AC drive overload pending
8: Set count value reached
9: Designated count value reached
10: Length reached
11: PLC cycle completed
12: Accumulative running time reached
13: Frequency limited
14: Torque limited
15: Ready for RUN
16: AI1 > AI2
17: Frequency upper limit reached
18: Frequency lower limit reached (no output at stop)
19: Undervoltage state output
20: Communication setting
23: Zero-speed running 2 (having output at stop)
24: Accumulative power-on time reached
25: Frequency-level detection 2 output
26: Frequency 1 reached
27: Frequency 2 reached
28: Current 1 reached
29: Current 2 reached
30: Timing reached
31: AI1 input limit exceeded
32: Load loss
33: Reverse running
34: Zero current state
35: IGBT temperature reached
36: Output current limit exceeded
37: Frequency lower limit reached (having output at stop)
38: Abnormality output (direct output at fault or warning)
39: Motor overheat pre-warning
40: Current running time reached
41: Fault output 2 (output at coast to stop/decelerate to stop, no
output at undervoltage)
43: Position lock enabled (deviation pulses < F6-25)
F5-02 Relay function selection
2
Setting range same as FMR
F5-04
DIO1 function selection
0