Appendix A Parameter Table
- 101 -
Para.
No.
Para. Name
Setting Range
Default
Property
F2-48
Speed loop bandwidth
setting value in inertia
auto-tuning (unit: Hz)
0.1 to 100.0
10.0 Hz
★
F2-50 Inertia auto-tuning
mode
0: Acceleration/deceleration mode
1: Triangular wave mode
0
★
F2-51
Inertia auto-tuning
acceleration/
deceleration coefficient
(unit: 0.1)
0.1 to 10.0
1.0
★
F2-52 Decoupling control
0: Disabled
1: Enabled
0
★
F2-53 Generating power limit
function
0: Disabled
1: Enabled
0
★
F2-54
Generating power limit
value
0.0 to 200.0%
Model
dependent
★
Group F3: V/F Control Parameters
F3-00
V/F curve setting
0: Linear V/F
1: Multi-point V/F
2: Square V/F
3: 1.2-power V/F
4: 1.4-power V/F
6: 1.6-power V/F
8: 1.8-power V/F
9: Reserved
10: V/F complete separation
11: V/F half separation
0
★
F3-01
Torque boost
0.0%: Fixed torque boost
0.1% to 30.0%
Model
dependent
☆
F3-02 Cut-off frequency of
torque boost
0.00 Hz to maximum frequency (F0-
10)
50.00 Hz
★
F3-03
Multi-point V/F
frequency 1
0.00 Hz to F3-05 (Multi-point V/F
frequency 2)
0.00 Hz
★
F3-04
Multi-point V/F voltage
1
0.0% to 100.0%
0.0%
★
F3-05
Multi-point V/F
frequency 2
F3-03 (Multi-point V/F frequency 1) to
F3-07 (Multi-point V/F frequency 3)
0.00 Hz
★
F3-06
Multi-point V/F voltage
2
0.0% to 100.0%
0.0%
★
F3-07
Multi-point V/F
frequency 3
F3-05 (Multi-point V/F frequency 2) to
F1-04 (Rated motor frequency)
0.00 Hz
★
F3-08
Multi-point V/F voltage
3
0.0% to 100.0%
0.0%
★