5 Quick Commissioning
- 63 -
Operation
Para.
No.
Parameter Name
Default
Commission
0: Digital setting (initial value F0-08 can be modified by the
operating panel or terminal UP/Down, non-retentive at power
failure)
1: Digital setting (initial value F0-08 can be modified by the
operating panel or terminal UP/Down, retentive at power failure)
2: AI1
3: AI2
4: Reserved
5: Pulse setting (DIO1)
6: Multi-reference setting
7: Simple PLC
8: PID
9: Communication setting
10: Synchronization control
If F0-08 is
frequency
reference
Set F0-08
F0-08 Preset frequency
50.00 Hz
0.00 Hz to F0-10 (Maximum frequency)
If AI1 is frequency
reference
Set AI1
F4-13
AI curve 1 minimum input
-10.00 V
0 V to F4-15 (AI1 maximum input)
F4-14 Corresponding percentage of AI1
minimum input
-100.0%
-100.0% to 100.0%
F4-15 AI1 maximum input
10.00 V
F4-13 (AI curve 1 minimum input) to 10.00 V
F4-16 Corresponding percentage of AI1
maximum input
100.0%
-100.0% to 100.0%
If AI2 is frequency
reference
Set AI2
F4-18 AI curve 2 minimum input
0.00 V
0.00 V to F4-20 (AI2 maximum input)
F4-19 Corresponding percentage of AI2
minimum input
0.0%
-100.0% to 100.0%
F4-20 AI2 maximum input
10.00 V