Appendix A Parameter Table
- 114 -
Para.
No.
Para. Name
Setting Range
Default
Property
F8-06
Deceleration time 3
0.0s to 6500.0s
Model
dependent
☆
F8-07
Acceleration time 4
0.0s to 6500.0s
Model
dependent
☆
F8-08 Deceleration time 4
0.0s to 6500.0s
Model
dependent
☆
F8-09 Frequency jump 1
0.00 Hz to maximum frequency (F0-10)
0.00 Hz
☆
F8-10 Frequency jump2
0.00 Hz to maximum frequency (F0-10)
0.00 Hz
☆
F8-11 Frequency jump band
0.00 Hz to maximum frequency (F0-10)
0.00 Hz
☆
F8-12
Forward/Reverse run
switchover dead-zone
time
0.0s to 3000.0s
0.0s
☆
F8-13
Reverse run control
0: Enabled
1: Disabled
0
☆
F8-14
Running mode when
frequency reference
lower than frequency
lower limit
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
0
☆
F8-16 Accumulative power-on
time threshold
0 to 65000h
0h
☆
F8-17
Accumulative running
time threshold
0 to 65000h
0h
☆
F8-18 Startup protection
0: Disabled
1: Enabled
0
☆
F8-19 Frequency detection
value 1 (FDT1)
0.00 Hz to maximum frequency (F0-10)
50.00 Hz
☆
F8-20 Frequency detection
hysteresis 1 (FDT1)
0.0% to 100.0% (FDT1 level)
5.0%
☆
F8-21
Detection width of
target frequency
reached
0.0% to 100.0% (maximum frequency
F0-10)
0.0%
☆
F8-22
Jump frequency
during acceleration/
deceleration
0: Disabled
1: Enabled
0
☆
F8-25
Switchover frequency
of acceleration time 1
and acceleration time 2
0.00 Hz to maximum frequency (F0-10)
0.00 Hz
☆
F8-26
Switchover frequency
of deceleration time 1
and deceleration time 2
0.00 Hz to maximum frequency (F0-10)
0.00 Hz
☆
F8-27
Set highest priority to
JOG function
0: Disabled
1: Enabled