Appendix A Parameter Table
- 93 -
Para.
No.
Para. Name
Setting Range
Default
Property
F0-03
Main frequency
reference setting
channel selection
0: Digital setting (initial value F0-08
can be modified by operating panel
or terminal UP/Down, non-retentive
at power failure)
1: Digital setting (initial value F0-08
can be modified by operating panel
or terminal UP/Down, retentive at
power failure)
2: AI1
3: AI2
4: Reserved
5: Pulse reference (DIO1)
6: Multi-reference
7: Simple PLC
8: PID reference
9: Communication setting
10: Synchronization control
0
★
F0-04
Auxiliary frequency
reference setting
channel selection
Same as F0-03
0
★
F0-05
Base value of range
of auxiliary frequency
reference for main and
auxiliary calculation
0: Maximum frequency (F0-10)
1: Main frequency reference
0
☆
F0-06
Range of auxiliary
frequency reference
for main and auxiliary
calculation
0% to 150%
100%
☆