Appendix A Parameter Table
- 120 -
Para.
No.
Para. Name
Setting Range
Default
Property
F9-53
Fault protection action
selection 6
Ones: Motor overheat (E45)
Tens: Reserved
Hundreds: Reserved
Thousands: Reserved
Ten thousands: Fan fault (E80)
05500
★
F9-54
Frequency selection for
continuing to run upon
fault
0: Current running frequency
1: Frequency reference
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
1
☆
F9-55 Backup frequency upon
abnormality
0.0% to 100.0% (maximum
frequency, F0-10)
100.0%
☆
F9-56 Type of motor
temperature sensor
0: No temperature sensor (AI1 input)
1: PT100
2: PT1000
0
☆
F9-57
Motor overheat
protection threshold
0° C to 200° C
110℃
☆
F9-58 Motor overheat pre-
warning threshold
0° C to 200° C
90℃
☆
F9-59 Power dip ride-through
function selection
0: Disabled
1: Decelerate
2: Decelerate to stop
0
★
F9-60
Threshold of power dip
ride- through function
disabled
80 to 100%
85%
☆
F9-61
Judging time of bus
voltage recovering from
power dip
0.0s to 100.0s
0.5s
☆
F9-62
Threshold of power dip
ride- through function
enabled
60% to 100% (standard bus voltage)
80%
☆
F9-64 Load loss detection
level
0.0 to 100.0%
10.0%
☆
F9-65 Load loss detection
time
0.1s to 60.0s
1.0s
☆
F9-67 Overspeed detection
level
0.0% to 50.0% (maximum frequency,
F0-10)
0.0%: no detection
5.0%
☆
F9-68
Overspeed detection
time
0.0s to 60.0s
1.0s
☆