3746-900 Panel Codes
Table
1-3 (Page 2 of 9). 3746 Model 900 Control Panel Code
Panel Code
Action to be Taken
0032327A or 0032327B
Error detected on hot plugging. Coupler 1 of CBSP is not a TIC3. Install a TIC3
coupler in position 07N-A1-F1.
0032327C
TIC3 of CBSP successfully hot-plugged.
0032327D
Error detected on hot plugging. Coupler 1 of CBSP has been hot-plugged but
cannot be accessed. Exchange the FRU Group 2518 on page 1-25, go to page
1-24.
003636600 to 00363661
Error detected with BATS. Exchange the FRU Group 2501 on page 1-25, go to
page 1-24.
00363667
Error detected with BATS. Exchange the FRU Group 2504 on page 1-25, go to
page 1-24.
00363669
Error detected with BATS. Exchange the FRU Group 2501 on page 1-25, go to
page 1-24.
0036366A
Error detected with BATS. Exchange the FRU Group 2501 on page 1-25, go to
page 1-24.
00363670
Error detected with BATS. Exchange the FRU Group 2501 on page 1-25, go to
page 1-24.
00363671
Error detected with BATS. Exchange the FRU Group 2501 on page 1-25, go to
page 1-24.
00363677
Error detected with BATS. Exchange the FRU Group 2501 on page 1-25, go to
page 1-24.
0036367F
BATS ended without error
00393908 to 0039390A
Error detected at IML. A microcode problem is suspected. Do an IML with diag, if
the same code is displayed contact your support structure.
0039390B
Error detected at IML. Exchange the FRU Group 2501 on page 1-25, go to page
1-24.
003939BB
Error detected at IML. TIC3 not present or not detected. Check the TIC3 plugging.
If TIC3 is present and correctly plugged exchange the FRU Group 2507 on
page 1-25, go to page 1-24.
003939C8 to 003939CB
Error detected at IML. Exchange the FRU Group 2501 on page 1-25, go to page
1-24.
003939E6
Error detected at IML. Exchange the FRU Group 2501 on page 1-25, go to page
1-24.
003939F3 to 003939F4
Error detected at IML. Exchange the FRU Group 2501 on page 1-25, go to page
1-24.
003939F8 to 003939FA
Do an IML with diag, if the same code is displayed a microcode problem is sus-
pected. Contact your support structure.
0050502A
A microcode problem is suspected. Contact your support structure.
04D50E02
Exchange the FRU Group 2505 on page 1-25, go to page 1-24.
04D50EDC
Exchange the FRU Group 2505 on page 1-25, go to page 1-24.
04D5D568
A microcode problem is suspected. Contact your support structure.
04D5D56E
The TIC3 of CBSP is missing at initialization. Check the plugging of TIC3 in posi-
tion 07N-A1-F1 and do an IML with diags. If the same error is reported exchange
the FRU Group 2506 on page 1-25, go to page 1-24.
04D5D57B
A microcode problem is suspected. Contact your support structure.
04D5D580
A microcode problem is suspected. Contact your support structure.
04D5D5B4
A microcode problem is suspected. Contact your support structure.
04D6D602
Do an IML with diag, if the same code is displayed a microcode problem is sus-
pected. Contact your support structure.
04D6D603
Do an IML with diag, if the same code is displayed exchange the FRU group 2505
on page 1-25, go to page 1-24. If after exchange the problem is still present
contact your support structure.
04D6D604
Do an IML with diag, if the same code is displayed exchange the FRU group 2505
on page 1-25, go to page 1-24. If after exchange the problem is still present
contact your support structure.
04D9D9A9
Error session. Do the problem determination using
Token-Ring Network, problem
Determination Guide SX27-3710. If the problem persists exchange the FRU group
2506 on page 1-25, go to page 1-24.
04D9D9AA
Duplicate token ring local address. Two machines are installed on the LAN with
the same token ring local address. Go to “MAP 2770: 3746-900 Duplicate Token
Ring Local Address” on page 2-106.
1-16
3746-900: Service Guide
Summary of Contents for FlashSystem 900
Page 1: ...3746 Nways Multiprotocol Controller Model 900 Service Guide SY33 2116 02...
Page 2: ......
Page 3: ...3746 Nways Multiprotocol Controller Model 900 Service Guide SY33 2116 02...
Page 14: ...xii 3746 900 Service Guide...
Page 16: ...xiv 3746 900 Service Guide...
Page 22: ...xx 3746 900 Service Guide...
Page 29: ...Safety Figure 0 3 Ground Wire Connection On Controller Expansion SAFETY xxvii...
Page 60: ...Safety lviii 3746 900 Service Guide...
Page 61: ...Safety SAFETY lix...
Page 62: ...Safety lx 3746 900 Service Guide...
Page 63: ...Safety SAFETY lxi...
Page 64: ...Safety lxii 3746 900 Service Guide...
Page 65: ...Safety SAFETY lxiii...
Page 66: ...Safety lxiv 3746 900 Service Guide...
Page 67: ...Safety...
Page 68: ...Safety lxvi 3746 900 Service Guide...
Page 69: ...Safety SAFETY lxvii...
Page 70: ...Safety lxviii 3746 900 Service Guide...
Page 71: ...Safety...
Page 72: ...Safety lxx 3746 900 Service Guide...
Page 73: ...Safety SAFETY lxxi...
Page 74: ...Safety lxxii 3746 900 Service Guide...
Page 75: ...Safety SAFETY lxxiii...
Page 76: ...Safety lxxiv 3746 900 Service Guide...
Page 77: ...Safety SAFETY lxxv...
Page 78: ...Safety lxxvi 3746 900 Service Guide...
Page 92: ...Safety xc 3746 900 Service Guide...
Page 94: ...Safety xcii 3746 900 Service Guide...
Page 129: ...3746 900 FRU Exchange 010 continued Go to MAP Ready LED ON on page 1 52 Chapter 1 START 1 35...
Page 276: ...3746 900 MAPs Figure 2 6 CP2 Circuit 2 18 3746 900 Service Guide...
Page 325: ...3746 900 MAPs 026 continued Go to Step 014 on page 2 65 Chapter 2 MAPs for FRU Isolation 2 67...
Page 340: ...3746 900 MAPs 113 continued Go to Step 001 on page 2 68 2 82 3746 900 Service Guide...
Page 414: ...Service Processor MAPs 2 156 3746 900 Service Guide...
Page 484: ...FRU Exchange Figure 4 16 3746 Model 9x0 CBSP Cassette 4 18 3746 900 Service Guide...
Page 495: ...FRU Exchange Figure 4 23 3746 900 Rear of DC Power Box Chapter 4 3746 900 FRU Exchange 4 29...
Page 510: ...FRU Exchange Figure 4 39 3746 900 LIC16 Coupler 4 44 3746 900 Service Guide...
Page 520: ...FRU Exchange Figure 4 45 3746 900 Transformer Handling 4 54 3746 900 Service Guide...
Page 522: ...FRU Exchange 4 56 3746 900 Service Guide...
Page 542: ......
Page 545: ......