iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
171
Parameter
Description
Timeout period
Timeout duration for connection test (set to
3s
by default)
Table 6-16
SNMP v3 device parameter description
Parameter
Description
Name
Device name
IP Address
Set this parameter to the device IP address.
Port
Set this parameter to the port number of the device. (set to
161
by
default)
Security Name
Set this parameter to the user name added in
SNMPv3
on the
WebUI
of the device.
Authentication
Protocol
Set this parameter to the authentication protocol set on the device.
The default selection is
SHA
.
Support
SHA
and
MD5
agreement.
Authentication
Password
Set this parameter to the
SHA
or
MD5
password set on the device.
Privacy Protocol
Set this parameter to the privacy protocol set on the device. The
default selection is
AES
.
Support
CBC_DES
,
AES128
,
AES192
, and
AES256
agreement.
Privacy Password
Set this parameter to the
AES
or
DES
password set on the device.
NOTE
You are advised to set
Authentication Password
and
Privacy Password
to
different values.
Timeout period
Timeout duration for connection test (set to
3s
by default)
Step 7
Click
Connection Test
to start the connection test.
Step 8
After the connection test is successful, click
in the toolbar to save the device
information.
For UPS, if a battery monitor unit (BMU) is connected, the BMU will be automatically created.
----End