iManager NetEco 6000
Device Installation and Commissioning Guide
8 FAQ
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
307
the following figure. This step uses the access controller that connects to the COM1 port
on the MUS02A3 expansion card as an example.
The default value of
COM1 Baud Rate
is
9600
. Change the value to
19200
.
Figure 8-13
Setting A8802RS access controller parameters on the ECC500
2.
Click
Submit
.
Step 3
Add the ECC500 on the NetEco.
1.
Choose
System
>
Configuration Management
>
Data Center Planning
from the main
menu. The
Data Center Planning
window is displayed.
2.
Create an equipment room, set its management properties, and save the setting.
3.
Click
Cabinet
, select
Design
, select
Collector
for
Device
, and drag the ECC500
collector to the cabinet.
4.
Set the management properties of the ECC500 collector and click
the mapping between the parameters on the ECC500 and those on the NetEco.
Table 8-3
Parameter mapping
Parameter on the ECC500
Parameter on the NetEco
SNMPv3 User Name
Security Name
MD5/SHA Password
Authentication Password
DES/AES Password
Privacy Password
SNMP Port Number
Port, set to 161 by default
Step 4
Add the A8802RS access controller on the NetEco.
1.
Choose
System
>
Configuration Management
>
Data Center Planning
from the main
menu and select the cabinet that houses the ECC500 collector.
2.
Select
Access Controller
for
Device
and drag the A8802RS access controller to the
management domain.
3.
Access the management properties. Set
IP Address
to the IP address of the ECC500
collector, set
Port
to the port number used by the access controller to connect to the
COM port, and click
Connection Test
.
When
Connection Success
is displayed, the connection is successful.
The RS485 communications card can be inserted into any one or more slots among slots 1-4 on the
ECC500 V6 collector. The RS485 port numbers vary based on slots.
collector slots.