iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
222
----End
6.4.3 Adding the Access Management System
6.4.3.1 Setting Monitoring Parameters for the A8802RS or A8804RS Access
Controller
Procedure
Step 1
Set the address of the access controller using the DIP toggle switches, as shown in
Table 6-34
Setting the address of the access controller
Address Value
Toggle switch 1
Toggle switch 2
0
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
Step 2
Set the baud rate of the access controller to
19200
. The preset data bit, stop bit, and check bit
are
8
,
1
, and
none respectively
.
For ECC collector settings, see
6.4.1.4 Setting RS485 Parameters for the ECC500 V6
----End
6.4.3.2 Setting Monitoring Parameters for the Shengjiu_MS899 Electronic
Door Lock
The Shengjiu MS899 electronic door lock supports a maximum of 16 users.
1.
The address of the MS899 electronic door lock is
1
, when creating an MS899 on the
NetEco, set
Device address
to the same value.
2.
Set the baud rate of the access controller to
9600
. The preset data bit, stop bit, and check
bit are
8
,
1
, and
none respectively
.
For ECC collector settings, see
Setting RS485 Parameters for the ECC500 V6
Collector
.
6.4.3.3 Creating an A8802RS/A8804RS Access Controller on the NetEco
Prerequisites
You have logged in to the NetEco client.
You have the operation rights for
Access Control Management
and
Data Center
Planning
.