iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
246
Enable Security Authentication
is set to
Enable
by default. If so, an authentication password must be
set. If
Enable Security Authentication
is set to
Disable
, there is no need to set an authentication
password but this is risky.
If the port has been used, you will be prompted that the transparent transmission function
cannot be enabled and you need to select an idle port.
Step 4
Log in to the NetEco WebUI as an administrator.
Step 5
Choose
Configuration
>
Configuration Management
>
Data Center Planning
. The
Data
Center Planning
window is displayed.
Step 6
Select the management domain to add a device. The management domain can be a modular,
rack, or equipment room.
Step 7
(Optional) If the management domain is a rack, click the management domain and choose
Design
under
. The page for adding a device is displayed. Otherwise, skip this step.
Step 8
In the lower-left corner of the page, click the
Device
tab.
Step 9
Click the drop-down list box in
Type
and select
Sensor
.
Step 10
In this example, a Polymer temperature and humidity (T/H) sensor is added in the equipment
room of the root node. Select the device to be added and drag its icon to the management
domain.
Step 11
Set management attributes.