iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
211
Step 2
Remove the cable connecting the independent deployment AI/DI unit and the ECC500
communications card, and reconnect the cable to restart the independent deployment AI/DI
unit.
----End
6.4.2.2.3 Creating a Temperature Sensor on the NetEco
Prerequisites
You have logged in to the NetEco client.
You have the operation rights for
Data Center Planning
.
You have created a management domain for the device to be added on the
Data Center
Planning
page.
Procedure
Step 1
Choose
Configuration
>
Configuration Management
>
Data Center Planning
from the
main menu. The
Data Center Planning
window is displayed.
Step 2
Select the management domain to add a device.
Step 3
If the management domain is a rack, click the management domain and choose
Design
under
. The page for adding a device is displayed. Otherwise, skip this step.
Step 4
In the lower-left corner of the page, click the
Device
tab.
Step 5
Click the drop-down list box in
Type
and select
Sensor
.
Step 6
Select the device to be added and drag its icon to the management domain.
To delete a device, click the device and choose
Delete
under
.
Step 7
Specify parameters shown in
in the right pane based on the following table. NTC
is used as an example.