iManager NetEco 6000
Device Installation and Commissioning Guide
8 FAQ
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
305
Figure 8-10
Setting SNMP parameters_02
5.
Click
Submit
.
----End
8.7 How Can I Commission a Device That Connects
Through the ECC500 RS485 Port?
Prerequisites
Cables are properly connected to the ECC500 and the device that connects to the RS485
port on the ECC500.
You have logged in to the NetEco client and have the operation rights for
System
and
Data Center Planning
.
Context
This topic uses the A8802RS access controller as an example for illustration. The actual
device prevails.
Procedure
Step 1
Set SNMP parameters on the ECC500.
1.
On the main menu, choose
System Settings
>
SNMP Settings
. Select
SNMPv3
for
SNMP Version
and enter
161
for
SNMP Port Number
.
2.
Click
Add
in
SNMPv3
, set
User Name
,
MD5/SHA Password
, and
DES/AES
Password
. Confirm
MD5/SHA Password
and
DES/AES Password
. Click
Confirm
.