iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
178
Parameter
Description
Security Name
Set this parameter to the user name added in
SNMPv3
on the
WebUI
of the device.
Authentication
Protocol
Set this parameter to the authentication protocol set on the device.
The default selection is
SHA
.
Support
SHA
and
MD5
agreement.
Authentication
Password
Set this parameter to the
SHA
or
MD5
password set on the device.
Privacy Protocol
Set this parameter to the privacy protocol set on the device. The
default selection is
AES
.
Support
CBC_DES
,
AES128
,
AES192
, and
AES256
agreement.
Privacy Password
Set this parameter to the
AES
or
DES
password set on the device.
NOTE
You are advised to set
Authentication Password
and
Privacy Password
to
different values.
Timeout period
Timeout duration for connection test (set to
3s
by default)
Step 8
Click
Connection Test
to start the connection test.
Step 9
After the connection test is successful, click
in the toolbar to save the device
information.
----End
6.3.7 Adding a RPDU
6.3.7.1 Setting RPDU_HUAWEI_PDU2000-32-1PH-20-4-M2 Monitoring
Parameters
Prerequisites
You have obtained the IP address (factory default: 192.168.1.45) of the PDU2000.
You have installed the hardware and powered on the PDU2000.
A PC with an IP address in the same network segment as that of the PDU2000 is
prepared, and the PC has connected to the PDU2000 over a switch.
You have obtained the planned IP address and subnet mask of the PDU2000.
Context
Set the PDU2000 IP address before you connect the PDU2000 to the NetEco.
Procedure
Step 1
Use a PC with an IP address in the same network segment as that of the PDU2000. Enter
http://
192.168.1.45
in the address bar, and press
Enter
on the keyboard.