iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
207
Table 6-27
Mapping between Extended Info tab name and slot number of the AI/DI expansion
card
Extended Info Tab Name
on the NetEco
Measurement Object
Slot Number of the
AI/DI Expansion Card
Extended Info/MUE05A1
21
1
Extended Info/MUE05A2
22
2
Extended Info/MUE05A3
23
3
Extended Info/MUE05A4
24
4
4.
Change the dry contact counter name of the collector in the corresponding text box.
For example, if the independent deployment AI/DI unit is MUE06A1 and the dry contact
is connected through the AI/DI_1 port, modify the counter name in the
MUE06A1_AI_DI_1
text box. After a dry contact signal name is modified, the alarm
name corresponding to the dry contact signal is automatically modified.
5.
Click
to save the changes.
Modifying Alarm Names for Dry Contacts on the NetEco (for V1.2)
1.
On the main menu, choose
Alarm
>
Alarm Operation
>
Alarm Settings
to go to the
Alarm Settings
page.
2.
In the navigation pane on the left, choose
Custom Alarm
>
Redefine Alarm
.
3.
Click
Create
.
4.
Click
Select Alarm
. In the displayed dialog box, select
Collector_HUAWEI_ECC500V6_SNMP
for
Device Type
on the left, select the alarm
name to be modified on the right, and click
OK
.
5.
Specify
New Alarm Name
,
Alarm Type
, and
Alarm Severity
, and click
Next
.
6.
Select an applicable scope.
Applicable
Scope
Description
All Objects
The alarm name modification applies to all ECC500 V6 devices in the
data center.
Custom
The alarm name modification applies to the ECC500 V6 devices in the
selected management domain.
6.4.2.1.7 Modifying Performance Counters for Dry Contacts on the NetEco
Prerequisites
You have logged in to the NetEco client.
You have the operation rights for
Data Center Planning
.
You have created an ECC500 collector in the
Date Center Planning
page.