iManager NetEco 6000
Device Installation and Commissioning Guide
3 Installing Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
22
Figure 3-11
Installing a temperature sensor
----End
3.6.2 Installing the Hydrogen Detection System
Context
The hydrogen detection system is used to detect the hydrogen density indoors. When the
hydrogen density exceeds the alarm threshold, the system generates alarms.
The hydrogen detection system is installed on the interior wall of the area to be detected.
Procedure
Step 1
Install four expansion bolts (M6x60) to the specified positions, align the four mounting ears
of the hydrogen detection system with the expansion bolts, and tighten the M6 nuts.