Step 2
When
Add
is displayed, set the device address by pressing
+
and
-
. When creating an ambient
temperature and humidity sensor on the NetEco, set
Device address
to the same value.
Step 3
Press
Set
.
Step 4
When
bAu
is displayed, retain the default value or change the baud rate by pressing
+
and
-
.
Set
BaudRate
for the collector port to the same value.
Baud rates 12, 24, 48, and 96 on the temperature and humidity sensor panel represent 1200, 2400,
4800, and 9600, respectively.
DataBit
,
StopBit
, and
Parity
for the ambient temperature and humidity sensor cannot be set on the
WebUI. Their values are
8
,
1
, and
None
respectively.
Step 5
Set RS485 port parameters for the collector based on the value of
BaudRate
,
DataBit
,
StopBit
, and
Parity
of the device. For ECC collector settings, see
Parameters for the ECC500 V6 Collector
----End
6.4.2.3.2 Creating a Temperature and Humidity Sensor on the NetEco
Prerequisites
You have logged in to the NetEco client.
You have the operation rights for
Data Center Planning
.
You have created a management domain for the device to be added on the
Data Center
Planning
page.
Procedure
Step 1
Choose
Configuration
>
Configuration Management
>
Data Center Planning
from the
main menu. The
Data Center Planning
window is displayed.
Step 2
Select the management domain to add a device.
Step 3
In the lower-left corner of the page, click the
Device
tab.
Step 4
Click the drop-down list box in
Type
and select
Sensor
.
Step 5
Select the device to be added and drag its icon to the management domain.
To delete a device, click the device and choose
Delete
under
.
Step 6
Specify parameters shown in
in the right pane based on the following table. The
T/H sensor complying with the MODBUS-RTU protocol is used as an example.