iManager NetEco 6000
Device Installation and Commissioning Guide
7 Device Maintenance
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
281
Step 7
Set the address of the access controller using the DIP toggle switches, as shown in
Table 7-16
Setting the address of the access controller
Address Value
Toggle switch 1
Toggle switch 2
0
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
Step 8
Set the baud rate of the access controller to
19200
. The preset data bit, stop bit, and check bit
are
8
,
1
, and
none respectively
.
----End
7.2.7.2 Replacing a Double-Door Magnetic Lock
Prerequisites
A double-door magnetic lock needs to be replaced.
Spare magnetic locks of the same model are available and functional.
Context
Prepare magnetic locks of the same model.
Recommended tools and materials: crimping tool, Phillips screwdriver, hex key (delivered
with the product package), step ladder (2 m).
Procedure
Step 1
Remove the cover of the magnetic lock, as shown in