4
2
OPTIONAL FUNCTION
NOTES:
This function is available when "4.1.3 Power Supply
ON/OFF 2 (after Power Failure)" is applied.
Picking up signal within 10 seconds after power supply
is turned ON is not available due to initializing of
components.
n
Remote Control 3 (Pulse Signal Input)
By using the signal from a building management system,
the air conditioners can be stopped. If a signal is input
during stoppage of air conditioner, the air conditioner
remains unchanged. The basic wiring and time chart are
shown below.
Ö
CAUTION:
Turn OFF the power source before setting the dip
switch.
Wiring Diagram Example of Remote Control 3:
NOTE:
The pulse width shall be wider than 200ms.
Time Chart:
NOTES:
This function is available when "4.1.3 Power Supply
ON/OFF 2 (after Power Failure)" is applied.
Picking up signal within 10 seconds after power supply
is turned ON is not available due to initializing of
components.
n
Cancellation of Commands from Remote Control
Switch after Forced Stoppage (Level Signal Input)
By using the signal from a building management system,
the air conditioners can be stopped and the commands
from the remote control switch are canceled. The basic
wiring and time chart are shown below. The required parts
are shown in Table 4. 1
Wiring Diagram Example:
Time Chart:
NOTE:
Picking up signal within 10 seconds after power supply
is turned ON is not available due to initializing of
components.
Set No.6 at ON Side
Indoor Unit PCB
3P Connector
Indoor Unit PCB
Time
Signal to 1 & 2 of
CN4
Control by R.C.S
Unit Operation
SS3: Remote Control ON/OFF
Control Circuit
Power
Source
SS3: Remote Control ON/OFF
Control Circuit
Power
Source
OFF
Cut JP5 of Indoor PCB
Indoor Unit PCB
3P Connector
SS3: Forced stoppage SW
Control Circuit
Power
Source
Time
Signal to 1 & 2 of
CN4
Control by R.C.S
Unit Operation
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...