TROUBLESHOOTING
61
Alarm Code
EE
Compressor Protection
This alarm code appears when one of the following alarms occurs three times within 6 hours, which may
result in serious compressor damages, if the outdoor unit is continuously operated without removing the
cause.
Alarm Code:
Content of Abnormality
02
Tripping of Protection Device in Outdoor Unit
07
Decrease in Discharge Gas Superheat
08
Increase in Discharge Gas Temperature
39
Abnormality of Running Current at Constant Comp.
43
Pressure Ratio Decrease Protection Activating
44
Low Pressure Increase Protection Activating
45
High Pressure Increase Protection Activating
46
High Pressure Decrease Protection Activating
47
Low Pressure Decrease Protection Activating
These alarms are able to be checked by the CHECK Mode 1. Follow the action indicated in each alarm chart.
These alarms are cleared only by turning OFF the main power switch to the system. However, careful
attention is required before starting, since there is a possibility which will result in serious damages to
the compressors.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...