WARNING: TURN OFF all power source switches
12. Check insulation of the terminal board with a megohm-
meter. Check to ensure that the insulation is greater than 1
M
W
when 500V is applied.
13. Check to ensure that water can flow smoothly after pouring
water on the drain pan.
14. Neutralization Treatment after Cleaning
The cleaning agent specified in the item, 2.10.1 is of the
neutral type. However, the cleaning water after use may be
not neutral.
Collect all cleaning water and make necessary
neutralization treatment for the cleaning water.
2.11
REMOVING REMOTE CONTROLER
2.11.1
REMOVING REMOTE CONTROL SWITCH
1. Remove the panel from the bracket.
a Snap out the bottom part of the panel from the bracket,
and
b unhook the top part.
2. Remove the connector with the cable from the panel.
3. Disassemble the panel by removing two screws.
NOTES:
When holding the printed circuit board by hand, hold the
edge and do not touch the electrical parts especially the
micro-computer part. The electrical parts may be broken by
the static electricity.
When reassembling, pay attention to the followings.
Blow the dust of each part away and then assembly them.
When tightening screws, pay attention not to break the
plastic part.
Panel
Wall
Bracket
Cord
Connector
M4 Screw
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...