1
TROUBLESHOOTING
49
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Excessively High or Low
Voltage of Power Source
operate within
380-145V±10%(50Hz)
380V±10%(60Hz)
220V±10%(60Hz)
Imbalance Among Phase
at Power Source
Adjust voltage between
each phase.
Excessively Large Running
Current of Compressor Motor
Excessively High
Discharge Pressure
Check for causes.
Melted Fuse for Power
Source
Replace the fuses.
Looseness of Screws for
Power Source
Tightly fix screws.
Single Phase Operation
Deterioration of Contact of
Magnetic Switch for
Compressor
Replace magnetic
contactor.
Seizure of Compressor
Bearing
Locked-up?
Replace compressor.
Insulation Failure of
Compressor Motor
Measure insulation
resistance.
Replace compressor.
Fault
Check continuity during
stoppage.
Replace CT when faulty.
Incorrect
Connection
Measure resistance by
tester.
Remove looseness and
replace connectors.
Overcurrent of
Compressor
Motor
Faulty CT
Incorrect
Wiring
Check wiring.
Correctly wiring.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...