5
6
FIELD WORK INSTRUCTION
5.9.
SERVICE & MAINTENANCE RECORD
No.
Check Item
Action
Judgement
1
Is service space
sufficient?
Yes
No
2
Short circuit of
Discharged Air?
Yes
No
3
Any Heat Influence
Yes
No
4
Is earth wire
connected?
Yes
No
5
Refrigeration Piping
Good
Not
Good
6
Fixing of Units
Good
Not
Good
7
Any Damage on
Outer or Internal
Surface?
Yes
No
8
Checking of Scew
and Bolts
Tighten if
loosen
Tightened
Not
Tightened
9
Tightening of
Terminal Screws
Tighten all
terminals
screws by
phillips driver
Tightened
Not
Tightened
10
Are compressor
terminals tighly
fixed?
Push all
terminals
Pushed
Not
Pushed
11
Insulation
Resistance
Measure Insulation
resistance by
Insulation
resistance-meter.
Comp. and Fan
Motor: greater than
3M
W
Others: greater
than 3M
W
Good
Not
Good
12
Does Drain Water
smoothly flow?
Check for smooth
flow by pouring
water.
Good
Not
Good
13
Check for Leakage
at compressor.
Check for any
Leakage
Good
Not
Good
14
Check for Leakage
at Outdoor heat
exchanger
ditto
Good
Not
Good
15
Check for Leakage
at Indoor heat
exchanger
ditto
Good
Not
Good
16
Check for Leakage
at 4-way valve
ditto
Good
Not
Good
17
Check for Leakage
at check valve
ditto
Good
Not
Good
18
Check for Leakage
at accumulator
ditto
Good
Not
Good
No.
Check Item
Action
Judgement
19
Check for Leakage
at Strainer
ditto
Good
Not
Good
20
Check for Leakage
at electronic Ex.
Valve
ditto
Good
Not
Good
21
Check for Leakage
at piping
ditto
Good
Not
Good
22
Check for direction
of fans
by Viewing or
Air Flow
Volume
Good
Not
Good
23
Voltage among
each Phase
Higherthan
220V
Good
Not
Good
24
Vibration and
Sound
Check fan,
compressor,
piping, etc
Good
Not
Good
25
Activation of each
Operation Mode
Check
Activation of
Cool, Heat,
Stop, and
Temp. switches
Good
Not
Good
26
High Pressure Cut-
out Switch
Check actual
activation value
Good
Not
Good
27
Check activation of
drain mechanism
Check it during
cooling
operation
Good
Not
Good
28
Indoor Inlet Air
Temp. DB/WB
(°C)DB
(°C)WB
29
Indoor Outlet Air
Temp. DB/WB
(°C)DB
(°C)WB
30
Outdoor Inlet Air
Temp. DB/WB
(°C)DB
(°C)WB
31
Outdoor Outlet Air
Temp. DB/WB
(°C)DB
(°C)WB
32
High Pressure
Switch
kg/cm²G
33
Low Pressure
Switch
kg/cm²G
34
Operating Voltage
V
35
Operating Current
A
36
Instruction for
cleaning of Air Filter
to client
Done
Not Yet
37
Instruction for
cleaning of Method
to client
Done
Not Yet
38
Instruction for
Operation to client
Done
Not Yet
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...