TROUBLESHOOTING
1.2.4
TROUBLESHOTING BY 7-SEGMENT DISPLAY
n
CHECKING METHOD BY 7-SEGMENT DISPLAY
By using the 7-segments and check switch (PSW) on the PCB1 in the Outdoor Unit, total quantity of combined Indoor Units, 7-
segments operation conditions and each part of refrigerant cycle can be checked.
PSW3
·
·
·
Backward
PSW2
·
·
·
Forward
n
To start checking, press the "PSW2"
switch for more than 3 seconds.
n
To proceed checking, press the
"PSW2" switch for less than 2
seconds.
n
To proceed reversely, press the
"PSW3" for less than 2 seconds.
n
To cancel this checking, press the
"PSW2" switch for more than 3
seconds. The display will be changed
to the indication one step before.
Then, press the PSW2"switch once
again for more than 3 seconds.
Checking Item
Checking contents
1
Output State of Outdoor
Micro-Computer
S C
ì ö
2
Total of Thermo - ON
Indoor Units Capacity
o P
2 6
000
~
240
(X
1/8
HP)
3
Running Frequency of
Inverter Compressor
MC1
H 1
1 0 0
000
~
115
(Hz)
4
Number of Running
Compressor
C C
2
0
~
4
to next page
PSW
7-Segments
Manual
Defrost
Check
PSW1
PSW2
PSW3
8 8 8
SEG3
SEG2
SEG1
PSW3
PSW2
PSW3
PSW2
PSW3
PSW2
PSW3
PSW2
PSW3
PSW2
PSW3
PSW2
PSW3
PSW2
PSW3
PSW2
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...