TROUBLESHOOTING
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Ref. Cycle is Different from
the Electrical System
Check ref. cycle and
electrical system.
Repair wiring.
Overcharged Refrigerant
Measure pressure. (Refer to
Figure in Test Run of TC.)
Correctly charge
refrigerant.
Faulty Ex. Valve
Refer to 1.3.6.
Replace ex. valve if faulty.
Fault
Replace PCB and check
operation.
Replace PCB if faulty.
Faulty PCB
Disconnected
Wires for Ex.
Valve Control
Check connections.
Repair wiring connection.
Fault
Measure resistance.
Replace thermistor if
faulty.
Incorrect
Mounting
Check mounting state.
Correctly mount
thermistor.
Decrease of
Discharge Gas
Superheat
Faulty
Discharge
Gas
Thermistor
Incorrect
Connection
Check connections.
Remove looseness,
replace connector or
repair connections