2
56
SERVICING
$
WARNING: TURN OFF all power source switches
8. After checking that no power is supplied, connect the drain
pipe and remove the insulation tape for the wiring
connectors and then mount the front cover correctly.
9. Check insulation of the terminal board in the electrical box.
If the insulation is greater than 1M
W
by a 500 Megohm-
meter, it is normal.
10. Neutralization Treatment after Cleaning
The cleaning agent specified in the item, 2.10.1 is of the
neutral type. However, the cleaning water after use may be
not neutral. Collect all cleaning water and make necessary
neutralization treatment for the cleaning water.
2.10.6
CLEANING CEILING TYPE INDOOR UNIT
■
Spread a vinyl sheet over the floor to avoid cleaning water
before this work.
1. Remove the left and right side covers according to page 2-
41 and the item, 2.8.2, "Removing Side Cover".
2. Remove the discharge deflector according to page 2-41
and the item, 2.8.3, "Removing Discharge Air Grille".
3. Open the intake air grille according to page 2-41 and the
item, 2.8.1, "Removing Air Filter".
4. Remove the lower cover and drain pan according to page
2-44 and the item 2.8.8, "Removing Thermistors for Liquid
Pipe and Gas Pipe".
5. Remove the indoor fan motor and fan assembly according
to page 2-42 and 2.8.4, "Removing Fan Motor".
6. Remove the partition plate 2 after removing two fixing
screws.
7. Remove the fixing plate for the fan after removing two
screws at the left and one screw at the right side partition.
8. Attach the drain pan and lower cover according to the
reverse procedures in the item, (4).
9. Cover all components except the drain pan with a vinyl
sheet avoid splashed cleaning water.
10. Spray the cleaning water over the fins from the rear side of
the heat exchanger. If the heat exchanger is heavily
covered with dust, use a brush to wipe off.
11. Cleaning with Clean Water
a. Operate the pump and clean the heat exchanger with
clean water completely.
b. Adjust pressure of the pump so as not to damage fins.
NOTES:
Wear gloves to avoid any injury during this work due to
sharp edge of fins.
If the cleaning water remains, fins will be corroded.
Adjust the pressure of the pump at 2.5 to 5.0 kg/cm² so as
not to damage fins.
Pay attention to the drain pan not to overflow.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...