1
TROUBLESHOOTING
53
Alarm Code
46
Activation to Protect System from Excessively Low Discharge
Pressure (for Protection of Refrigerant Shortage)
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the compressor is operated under the conditions higher than 0.6MPa
(6kgf/cm²G) for an hour.
Discharge
Pressure
Voltage between
#2 and #3 of CN7
Outdoor Air Temperature (°C)
Is the amount of refrigerant correct?
No
Correctly charge refrigerant.
Yes
Connect pressure gauge at the check
joint of the compressor discharge pipe.
Yes
Is the high-pressure in the alarm
area?
Yes
Check for leakage of refrigerant.
No
Is the connector CN7 of outdoor unit
PCB1 loose?
yes
Plug the connector CN7 correctly.
No
Is the high-pressure sensor pipe
clogged?
Yes
Remove clogging.
No
Is voltage between #1 and #3 of the
connector CN7 of outdoor unit PCB1
12V, and voltage between #2 and #3
in the alarm area?
Yes
Replace the high-pressure sensor.
No
Check the outdoor unit PCB1 by
self-checking. Replace it if faulty.
Alarm Area
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...