4
OPTIONAL FUNCTION
11
4.2.10.
PICKING UP SIGNALS FROM OUTDOOR
UNIT PRINTED CIRCUIT BOARD
The parts applied to picking up operation signals are shown
in Table 4. 5
Table 4. 5 Main Required Part
Part Name
Manufacturer etc.
Auxiliary Relay
OMRON High Power Relay Model:
LY2F DC12V
n
Picking Up Alarm Signal
With this procedure the Outdoor unit alarm signals can be
picked up. The method is explained in the figure below.
The required part is indicated in Table 4. 5. Connecting
relay contactors (RYa) are closed at the time of alarm.
(When either one of the units issues an alarm, an alarm
signal is indicated.)
n
Picking Up Operation Signal
With this procedure the operation signal of cooling or
heating can be picked up. The method for picking up the
signal is explained in the figure below. The required part is
the same as in Table 4.5. Connecting relay contactors RYa
are closed at the time of cooling or heating. These signals
can be applied to the operation of circulators and
humidifiers.
n
Picking Up Compressor ON Signal
With this procedure the compressor signal can be picked
up. The method is explained in the figure below. The
required part is indicated in Table 4. 5. Connecting relay
contactors (RYa) are closed at the time of compressor
running. This signal can be applied to the check of signals
at the time of remote controlling and to the fan interlock of
outdoor fresh air.
n
Picking Up Defrosting Signal
With this procedure the Defrosting signal can be picked up.
The method is explained in the figure below. The required
part is indicated in Table 4. 5. Connecting relay contactors
(RYa) are closed at the time of defrosting.
Aux. Relay
3P Connector Housing
JST-XARP-03V
(Contact SXA-001T-P0.6)
Connector
CN16
Outdoor Unit PCB
Power supply
Board of Outdoor
Unit (PCB1)
Aux. Relay
3P Connector Housing
JST-XARP-03V
(Contact SXA-001T-P0.6)
Connector
CN16
Outdoor Unit PCB
Power supply
Board of Outdoor
Unit (PCB1)
Aux. Relay
3P Connector Housing
JST-XARP-03V
(Contact SXA-001T-P0.6)
Connector
CN16
Outdoor Unit PCB
Power supply
Board of Outdoor
Unit (PCB1)
Aux. Relay
3P Connector Housing
JST-XARP-03V
(Contact SXA-001T-P0.6)
Connector
CN16
Outdoor Unit PCB
Power supply
Board of Outdoor
Unit (PCB1)
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...