TROUBLESHOOTING
Alarm Code
02
Activation of Safety Device in Outdoor Unit
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm is indicated when one of safety devices is activated during compressor running.
Does CMC1 ON
when startting?
No
Is Y52C1 of
7-segments ON? (when
in check mode "SC")
No
Faulty PCB1
Yes
No
Yes
Is the voltage
between PCN3#1 and
faston terminal "N"
220V or 240V during
Y52C1 ON?
No
Faulty PCB1
Yes
No (No Looseness)
Faulty PCB1
Is the protective
device still operating?
(No continuity between
#1 and #3 of PCN2)
No
Is PCN3 or PCN2
loosened?
Yes
Restart after
connecting PCN3 or
PCN 2 correctly.
Yes
Does CMC1 turn ON
for more than 3
seconds
No Voltage
Faulty PCB1
Yes
Normal PCB1
Check activation of the following safety devices. Remove the cause after checking.
High Pressure Switch
(PSH: 3.0MPa (30 kgf/cm²G) for FS3 Series / 3.3MPa (33 kgf/cm²G) for FSG Series)
Check Item
Power Suplly
Connector for CMC1
Faston Terminal
380-415V 50Hz
PCN3
N
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...