TROUBLESHOOTING
Alarm Code
13
Abnormality of Thermistor for Indoor Unit Heat Exchanger Liquid
Refrigerant Pipe Temperature (Freeze Protection Thermistor)
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the thermistor is short-circuited (less than 0.24 k
W
) or cut (greater than
840 k
W
) during the cooling or heating operation. The system is automatically restarted when the fault is
removed.
Is it connected to THM3
(intake) of PCB.
No
Connect it.
Yes
Is resistance of THM3
between 0.24k
W
and 840k
W
?
No
Faulty Thermistor
Yes
Refer to page 1-34 for
thermistor resistance
Faulty PCB
.
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Fault
Check resistance.
Replace thermistor if
faulty.
Faulty Intake
Air Thermistor
Incorrect Connection
Check connection.
Repair wiring and
connections.
Faulty PCB
Replace PCB and Check
operation
Replace PCB if faulty
In case of 4-Way
Cassette
Freeze Protection
Thermistor (THM3)
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...