TROUBLESHOOTING
73
n
RUNNING CURRENT OF COMPRESSOR
n
Inverter Primary Current
The inverter primary current is estimated from the
running current of the compressor MC1 indicated on
7-segments, as the right chart shows.
n
Indicated Running Current of Compressor MC2,
MC3, MC4
The running current of the compressor MC2, MC3,
MC4, is detected by current sensor. (CT2 ~ CT4)
Inverte
r Pr
imary Curren
t (A)
Running Current of Compressor MC1
indicated on 7-segment
n
Cause of Stoppage for Inverter (Content of Check Item "
÷ ó C
")
Remark
Code
Cause
Cause of Stoppage for
Corresponding Unit
Indication
during Retry
Alarm Code
1
Automatic Stoppage of Transistor Module
(IPM Error)
(Over Current, Decrease Voltage, Increase
Temperature)
17
P 17
53
2
Instantaneous Over Current
17
P 17
52
4
Electronic Thermal Activation
17
P 17
52
5
Inverter Voltage Decrease
18
P 18
06
6
Excessively High Voltage
18
P 18
06
8
Abnormal Current Sensor
17
P 17
51
9
Instantaneous Power failure Detection
18
-
-
11
Reset of Micro-Computer for Inverter
18
-
-
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...