
5
2
FIELD WORK INSTRUCTION
5.3.
ABNORMALLY HIGH OPERATING SOUND (IN-THE-CEILING TYPE INDOOR UNIT)
n
Question and Answer for Field Work
Example 3: Abnormally High Operating Sound (In-the-Ceiling Type Indoor Unit)
Phenomenon
Operating sound during "Hi" speed was abnormally high.
Cause
The indoor units was installed without ducts. Due to almost no external static pressure,
abnormally big air volume was supplied, resulting in higher air speed through the heat
exchanger.
Countermeasure
In order to reduce air flow, a plate as a damper at the discharge side was added.
Remarks
Please note that running current is increased when no external pressure is given to the
indoor unit, resulting in overheating.
5.4.
ALARM CODE "31"
n
Question and Answer for Field Work
Example 4: Alarm Code "31"
Phenomenon
Alarm code "31" sometimes occurred and the system was stopped.
Cause
Combination of the indoor and outdoor unit was as follows.
This system was used in a tenant building. One of tenant’s customers cut out the power
switch for the indoor unit while other indoor units are running, resulting in different total indoor
unit capacity setting in the same refrigerant cycle.
Countermeasure
All the main power switches for the indoor units were always ON.
Indoor Unit
Damper
A. Filter
ON
ON
OFF
I.U.
ON
I.U.
ON
I.U.
ON
O.U.
Power
Source
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...