1
TROUBLESHOOTING
59
Alarm Code
59
Abnormality of AC Chopper Circuit Board
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when a current value of AC chopper becomes
less than 0.5A when outdoor
unit fan is operating, or
ó
more than 2A while outdoor unit fan stops.
Is outdoor unit fan operating
during the indication
of alarm code.
Yes
Abnormality of AC chopper
circuit board (PCB2).
No
Is outdoor unit fan operated for
more than 2 seconds when the
unit is restarted?
Yes
Is the connection of CT5 at
outdoor circuit board (PCB1)
right?
No
Connect CT5 correctly.
Yes
No
Abnormality of CT5.
Is the connection of CN13 at
outdoor unit circuit board (PCB1)
and CN201 at AC chopper circuit
board right?
No
Connect correctly.
Yes
Is the connection of S3, R3 at
outdoor unit circuit board (PCB1) or
faston of EF5 and S1, R1 at AC
chopper circuit board right?
No
Connect correctly.
Yes
Is the fuse of EF 5 melted?
Yes
Replace fuse.
No
Is the connection of MAIN1,
COM1, SUB1 at AC chopper
circuit board right?
No
Connect correctly.
Yes
Is the connection of relay
connector CN1 for outdoor fan
motor right?
No
Connect correctly.
Yes
Faulty AC chopper. Replace the
AC chopper.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...